WEINTEK-logo

WEINTEK KEYENCE KV-8000-KV-X Simbolički Ethernet programabilni logički kontroler

WEINTEK-KEYENCE-KV-8000-KV-X-Symbolic-Ethernet-Programmable-Logic-Controller-product

Tehnički podaci

Upute za instalaciju

Postavke HMI-ja: 

Parametri Preporučeno Mogućnosti Bilješke
tip PLC-a KEYENCE KV-8000/KV-X (Simbolički) (Ethernet)
PLC I/F Ethernet
Luka br. 8500
Vrsta uređaja KV8000 KV8000 / KVX
On-line simulator Da Multi-HMI povezivanje Da

Izvoz Tags:

Softver koji KV STUDIO kreira tag:

  1. Variable -> Cerected tag na globalnoj ili lokalnoj tablici.WEINTEK-KEYENCE-KV-8000-KV-X-Symbolic-Ethernet-Programmable-Logic-Controller-fig1
  2. Support Sturcutre address. WEINTEK-KEYENCE-KV-8000-KV-X-Symbolic-Ethernet-Programmable-Logic-Controller-fig2
  3. Izvoz tag: File -> Izlaz CSV/TXT file -> Varijabilne informacije WEINTEK-KEYENCE-KV-8000-KV-X-Symbolic-Ethernet-Programmable-Logic-Controller-fig3

Uvoz Tags:

  1. In EasyBuilder Pro -> System Parameter Settings -> New Driver (KV-8000) -> Import Tags. WEINTEK-KEYENCE-KV-8000-KV-X-Symbolic-Ethernet-Programmable-Logic-Controller-fig4
  2. Odaberite .txt datoteku file uvoziti. WEINTEK-KEYENCE-KV-8000-KV-X-Symbolic-Ethernet-Programmable-Logic-Controller-fig5
  3. Uvezite neke ili sve od tags WEINTEK-KEYENCE-KV-8000-KV-X-Symbolic-Ethernet-Programmable-Logic-Controller-fig6
  4. Odaberite tag želite uvesti Tag Upravitelju, pritisnite OK. WEINTEK-KEYENCE-KV-8000-KV-X-Symbolic-Ethernet-Programmable-Logic-Controller-fig7
  5. Uvozni tag informacije uspješno. WEINTEK-KEYENCE-KV-8000-KV-X-Symbolic-Ethernet-Programmable-Logic-Controller-fig8

Podrška Vrsta uređaja

Vrsta podataka EasyBuilder format podataka dopis
BOOL malo
INT 16-bitni BCD, hex, binarni, s predznakom 16-bitni
UINT 16-bitni BCD, hex, binarni, bez predznaka 16-bitni
DINT 32-bitni BCD, hex, binarni, s predznakom 32-bitni
UDINT 32-bitni BCD, hex, binarni, bez predznaka 32-bitni
STVARAN 32-bitni float 32-bitni
LSTVARNO 64-bitni float 64-bitni *Napomena1
NIZ Niz riječi za ASCII unos i prikaz *Napomena2
 

Niz

BOOL, INT, UINT, DINT, UDINT, REAL,

LREAL, Struktura

*Napomena3

 

Struktura

BOOL, INT, UINT, DINT,UDINT, REAL, LREAL, STRING

Niz

  • Napomena 1: EBPro V6.03.02 ili noviji podržava tip podataka od 64 bita (samo cMT serija), ali imajte na umu da je raspon ograničenja adrese maksimalno 48 bita.
  • Napomena 2: String In EasyBuilder Pro, only even addresses can be selected, and support string length up to 2000.WEINTEK-KEYENCE-KV-8000-KV-X-Symbolic-Ethernet-Programmable-Logic-Controller-fig9
  • Napomena 3: Support 1~3D array, 4D arrays and above cannot be imported.

Dijagram ožičenja

Ethernet kabel:

WEINTEK-KEYENCE-KV-8000-KV-X-Symbolic-Ethernet-Programmable-Logic-Controller-fig10

FAQ

How do I connect multiple HMIs?

You can connect multiple HMIs using the on-line simulator option in the HMI settings.

What is the maximum string length supported for STRING data type?

In EasyBuilder Pro, only even addresses can be selected, and it supports string length up to 2000.